description1
DescriptionDescription
01Huyssen’s Din Rail power supply has excellent performance and various protection functions, ensuring equipment safety in all aspects. Moreover, its working temperature range is -25 ℃~+70 ℃, and it is not afraid of extreme cold and heat. It has a 3000V surge protection capability and can operate stably even in harsh environments. It is increasingly adopted by enterprises in fields such as industrial automation, intelligent warehousing, and industrial robots, etc. With the rich design experience of our technical personnel in the field of power supply, we are able to provide customers with highly customized power solutions.
FeaturesFeatures
01SpecificationsSpecifications
|
MODEL |
NDR-120-12 |
NDR-120-24 |
NDR-120-48 |
|
|
OUTPUT |
|
12V |
24V |
48V |
|
CURRENT CURRENT |
10A |
5A |
2.5A |
|
|
CURRENT RANGE |
0~10A |
0~5A |
0~2.5A |
|
|
RATED POWER |
120W |
120W |
120W |
|
|
RIPPLE & NOISE |
100mVp-p |
120mVp-p |
150mVp-p |
|
|
VOLTAGE ADJ. RANGE |
12~14V |
24~48V |
48~55V |
|
|
VOLTAGE TOLERANCE |
±2.0% |
±1.0% |
±1.0% |
|
|
LINE REGULATION |
±0.5% |
±0.5% |
±0.5% |
|
|
LOAD REGULATION |
±1.0% |
±1.0% |
±1.0% |
|
|
SETUP, RISE TIME |
1200ms, 60ms/230VAC 2500ms, 60ms/115VAC at full load |
|||
|
HOLD UP TIME |
16ms/230VAC, 10ms/115VAC at full load |
|||
|
INPUT |
VOLTAGE RANGE |
90~264VAC 127~370VDC [DC input operation possible by connecting AC/L(+),AC/N(-)] |
||
|
FREQUENCY RANGE |
47~63Hz |
|||
|
EFFICIENCY |
85.50% |
88% |
89% |
|
|
AC CURRENT |
2.25A/115VAC 1.3A/230VAC |
|||
|
INRUSH CURRENT |
20A/115VAC 35A/230VAC |
|||
|
LEAKAGE CURRENT |
<1MA/240VAC |
|||
|
PROTECTION |
OVRELOAD |
105~130% rated output power |
||
|
Protection type: Constant current limiting, recovers automatically after fault condition is removed |
||||
|
OVER VOLTAGE |
14~17V |
29~33V |
56~65V |
|
|
Protection type: Shut down o/p voltage, re-power on to recover |
||||
|
OVER TEMPERATURE |
Protection type: Shut down o/p voltage, re-power on to recover |
|||
|
ENVIRONMENT |
WORKING TEMP |
-20~+70°C (Refer to "Derating Curve") |
||
|
WORING HUMIDITY |
20~95% RH non-condensing |
|||
|
STORAGE TEMP., HUMIDITY |
-40~+85℃,10~95%RH |
|||
|
TEMP.COFFICIENT |
±0.03%,℃(0-50℃) |
|||
|
VIBRATION |
Component: 10~500Hz, 2G 10min/1 cycle,60min, each along X,Y,Z axes; Mounting Compliance to IEC60068-2-6 |
|||
|
SAFETY& EMC |
SAFETY STANDARDS |
UI508, TUV EN60950-1 approved |
||
|
WITHSTAND VOLTAGE |
I/P-O/P 3KVAC I/P-FG 2KVAC O/P-FG 0.5KVAC |
|||
|
ISOLATION RESISTANCE |
I/P-O/P I/P-FG,O/P-FG>100M Ohms / 500VDC / 25°C / 70% RH |
|||
|
EMC EMISSION |
Compliance to EN55022, EN 61204-3 ClassB, EN61000-3-2 |
|||
|
EMC IMMUNITY |
Compliance to EN 61000-4-2,3,4,5,6,8,11 EN55024, EN61000-6-2(EN50082-2), EN1204-3, heavy industry level, criteria A |
|||
|
OTHERS |
MTBF |
456.3K, hrs min. MIL-HDBK-247F |
||
|
DIMENSION |
40*125.2*113.5mm(W*H*D) |
|||
|
PACKING |
0.6Kg. 20pcs/13Kg/1.16CUFT |
|||
Product sizeProduct size


mandy@huyssenpower.com
0086-13570841067
AC/DC Power Supply
AC to DC Power Supply 0-48V 4000W with High PFC
3000W 60V Switching Power Supply
DC 12V 83.3A 1000W AC/DC Switch Mode Power Supply
AC to DC 36V 1500W Switch Mode Power Supply
AC DC Power Supply S Series
SMPS DC 60V 20A 1200W Switching Power Supply
ACDC 24V 500W High Quality Switching Power Supply
Din Rail Power Supply
Din Rail Power Supply 12V 60W MDR-60-12
24V 60W Din Rail power supply MDR-60-24
12V 240W din rail power supply
DR-120-24 Din rail power supply
NDR-480-48 Din rail power supply
DC Power Supply
DC 100V 15KW Programmable Power Supply
app_imgs
app_imgs
DC 200V 60KW programmable power supply
DC 100V 1000A 100KW programmable power supply
Open Frame Power Supply
On Board Charger
Buck Converter DC input 18-36V to DC 5V60A 300W SD-350C-5
Buck Converter DC Input 200-500V to DC Output 3kW 0-32V for EV


top